Solomed, Sofia. The site’s cooling plant – two chillers – stands outdoors, close to a residential building.
An official measurement by an accredited inspection body showed 61.2 dB(A) at the dwellings (point IT1) against a limit of 55 dB(A) – an exceedance of 6 dB. Right next to the chillers the level was 72.4 dB(A).
The client came to us with the report in hand. The task was clear: a solution that brings the noise below the limit and is proven by a new official measurement.
The chillers stay where they are and must run without restrictions. They are surrounded by walls that reflect the noise. A ramp runs above them – point IT4 is on it, at a height of 4 m. The barrier had to leave access for servicing the machines.
We measured the noise at the same points as the inspection body and made a calculated prediction for a noise barrier around the chillers.
We agreed the prediction for each point in advance with the inspection body that carries out the official measurement: 52 dB(A) at the dwellings, 57 dB(A) at IT2, 63 dB(A) next to the chillers and 50 dB(A) on the ramp.
The barrier was built to the design. At the client’s explicit request, a drainage gap was left at its base for the yard.
After installation, the inspection body carried out a control measurement at the same points. Results in dB(A):
| Point | Before | Prediction | After |
|---|---|---|---|
| IT1 – at the dwellings (limit 55) | 61,2 | 52 | 55,0 |
| IT2 | 66,7 | 57 | 60,5 |
| IT3 – next to the chillers | 72,4 | 63 | 63,3 |
| IT4 – on the ramp | 54,0 | 50 | 50,0 |
At the dwellings the noise dropped by 6 dB – from 61.2 to 55,0 dB(A), i.e. to the limit value. Next to the chillers and on the ramp the prediction was met.
Honestly about the difference: at the dwellings the prediction was 52 dB(A) and we achieved 55.0. The reason is the drainage gap the client asked to keep – noise passes around the barrier through it. We show the result as measured.
Background noise during the measurement: 44.1 dB(A).
A walk around the noise barrier and the chillers behind it, with the sound on site. The sound was recorded on a phone: it gives an idea of what the noise is like, but not how loud it is – the phone evens out the recording level by itself. The measured levels are in the table above.
Similar project? See our service HVAC and Air Conditioning Systems or contact us via the enquiry form.
"*" indicates required fields
To ensure the best experience, we use technologies such as cookies to store and/or access information on your device. Consent to these technologies will allow us to process data such as browsing behavior or unique identifiers on this website. Disagreement or withdrawal of consent may adversely affect certain features and functions.