Do you have questions ?

Church Hall Acoustics – EPC Varna

The Challenge

The Evangelical Pentecostal Church in Varna uses its hall for services with speech and live music, with a sound system. The hall is fairly new – about 1,630 m³ – but the sound in it “echoed”: speech was hard to understand and the music became blurred.

On 27.03.2023 we measured the hall together with its sound system at more than 20 points. The reverberation time was about 2.0–2.1 s at 500–1000 Hz, there was echo at some points, and speech intelligibility was low.

Our Solution

We built a 3D model of the hall and checked it against the measurement. The hall is used in three modes – rehearsals, about 40% and full occupancy – and we calculated each of them. We took the target values from the Austrian standard ÖNORM B 8115-3 for rehearsal and performance halls. Bulgaria has no mandatory limit for such a hall, so we use it as a reference.

We compared four options by cost and effect. For the chosen solution the model gives a reverberation time of about 1.0–1.1 s at 500–1000 Hz and speech intelligibility (STI) up to 0.70 – half the decay time measured.

The Execution

We installed the final option:

  • fabric-covered acoustic wall panels, 6 cm thick, with 4 cm PET wool 2 cm off the wall;
  • 20 cm low-frequency panels in selected areas – for the low frequencies from the sound system;
  • hanging panels in the recesses above the stage and the balcony;
  • plywood ceiling panels, made and varnished on site.

By calculation, the minimum panel area was 120 m². The panels are our own production.

Result. On 02.08.2023 we measured the hall again at 17 points, in the same mode – empty hall. The reverberation time fell by about half and came within the target range of ÖNORM B 8115-3 from 100 Hz upwards:

Frequency, Hz125250500100020004000
Before (27.03.2023), s≈ 1,8≈ 1,8≈ 2,0≈ 2,1≈ 1,9≈ 1,6
After (02.08.2023), s1,301,100,980,980,930,77

Values are averaged over all points, in octave bands. The measurement is an engineering assessment (REW, 1/3 octave), not an accredited report. “Before” was read from the graph in the project report, so it is rounded. The measured “after” matches the model’s prediction (about 1.0–1.1 s).

Similar problem? See Acoustics and Soundproofing for Public Buildings or contact us via the enquiry form.

What the Client Says

“It is my great pleasure to recommend their work and expertise. No matter the circumstances you are in or what you may need, these are the people who can help you.”

– Pastor Miroslav Marinov

Contact Us

телефон - икона

Contact Phone

0883 40 00 61

адрес - икона

Address

NPZ Iskar, 1 "5004" Street, 1528, Sofia, Bulgaria

"*" indicates required fields

This field is for validation purposes and should be left unchanged.
So that we can call you to clarify details.
Drop files here or
Accepted file types: jpg, jpeg, png, pdf, Max. file size: 20 MB.